PVC Insulated Non- Armoured Power
Cables (Copper Conductor)- Three Core
|
Conductor
|
Nominal insulation thickness
mm
|
Approx. overall diameter
mm
|
Approx. cable weight
kg[km
150
|
Electricalcharacteristics
|
|
Size
mm2
|
Shape of conductor
|
Current Ranting
|
Conduction Resistance
|
Reactance at
50Hz
n/Km
|
Short circuit current For 1sec
KA
|
|
In air at
40°C
A
|
In the ground at
25°C
A
|
D.Cat
20°C
n/Km
|
50 Hz at
90°C
n/Km
|
|
1.5mm2
|
Circular
Stranded
|
0.70
|
11.5
|
22
|
29
|
12.1
|
15.4
|
0.1020
|
0.21
|
|
2.5mm2
|
Circular
Stranded
|
0.70
|
12.0
|
185
|
29
|
37
|
7.41
|
9.45
|
0.0932
|
0.36
|
|
4mm 2
|
Circular
Stranded
|
0.70
|
13.0
|
240
|
38
|
49
|
4.61
|
5.88
|
0.0875
|
0.57
|
|
6mm 2
|
Circular
Stranded
|
0.70
|
14.5
|
315
|
48
|
61
|
3.08
|
3.93
|
0.0837
|
0.85
|
|
10mm2
|
Circular
Stranded
|
0.70
|
16.5
|
465
|
65
|
81
|
1.83
|
2.33
|
0.0785
|
1.42
|
|
16mm2
|
Circular
Stranded
|
0.70
|
18.0
|
645
|
88
|
100
|
1.15
|
1.47
|
0.0761
|
2.28
|
PVC Insulated Non- Armoured Power Cables (Copper Conductor)- Four Core
|
Conductor
|
Nominal insulation thickness
mm
|
Approx. overall diameter
mm
|
Approx. cable weight
kg[km
180
|
Electricalcharacteristics
|
|
Size
mm2
|
Shape of conductor
|
Current Ranting
|
Conduction Resistance
|
Reactance at
50Hz
n/Km
|
Short circuit current For 1sec
KA
|
|
In air at
40°C
A
|
In the ground at
25°C
A
|
D.C at
20°C
n/Km
|
50 Hz at
90°C
n/Km
|
|
1.5mm2
|
Circular
Stranded
|
0.70
|
12.5
|
22
|
29
|
12.1
|
15.4
|
0.1020
|
0.21
|
|
2.5mm2
|
Circular
Stranded
|
0.70
|
13.5
|
220
|
29
|
37
|
7.41
|
9.45
|
0.0932
|
0.36
|
|
4mm 2
|
Circular
Stranded
|
0.70
|
14.5
|
300
|
38
|
49
|
4.61
|
5.88
|
0.0875
|
0.57
|
|
6mm 2
|
Circular
Stranded
|
0.70
|
16.0
|
400
|
48
|
61
|
3.08
|
3.93
|
0.0837
|
0.85
|
|
10mm2
|
Circular
Stranded
|
0.70
|
17.5
|
580
|
65
|
81
|
1.83
|
2.33
|
0.0785
|
1.42
|
|
16mm2
|
Circular
Stranded
|
0.70
|
19.5
|
820
|
88
|
100
|
1.15
|
1.47
|
0.0761
|
2.28
|